8) Wiring Installation Upon installation maximum cable lengths must be adhered to, use the following table to calculate the maximum cable lengths, taking in to account the cross section of the cables.

Cross Section

3 wire

5 wire

3 wire

5 wire

3 wire 4mm 2

5 wire 6mm 2

1.5mm 2

1.5mm 2

2.5mm 2

2.5mm 2

Actuator current Amps

2 wires in parallel

2 wires in parallel

1 2 3 4 5 6 7 8

105.00m 210.00m 175.00m 350.00m 280.00m 420.00m

52.50m 35.00m 26.25m 21.00m 17.50m 15.00m 13.10m

105.00m 70.00m 52.50m 42.00m 35.00m 30.00m 26.20m

87.50m 58.33m 43.75m 35.00m 29.17m 25.00m 21.80m

175.00m 140.00m 210.00m

116.67m 87.50m 70.00m 58.33m 50.00m 43.75m

93.33m 70.00m 56.00m 46.67m 40.00m 35.00m

140.00m 105.00m 84.00m 70.00m 60.00m 52.50m

(For ambient temperatures of 25 ° C) If the above table does not correspond to your system design the following calculations can be used for cable length: Maximum permissible voltage drop in the cable: 2.5V Max. cable length = permissible voltage drop (2.5) x conductivity of copper (56) x Cable cross-sectional area (A) Max. Actuator current total (I) x2

The cable length from the actuator to junction box should not exceed 10m,